500 eKW D500 GC Diesel Generator Set

D500GC Diesel Generator
MAXIMUM RATING
500 ekW

MINIMUM RATING
500 ekW

EMISSIONS/FUEL STRATEGY
EPA Stationary Emergency

OVERVIEW

Built to meet your needs for standby applications, the D500 GC diesel generator set provides a reliable source of power: 500 ekW at 60 Hz.

Built to accept 100% rated load in one step, this generator set meets the ISO 8528-5 transient response requirements.

These engines were certified for U.S. EPA Certified for Stationary Emergency Use – Tier 2 or Tier 3 Nonroad Equivalent Emission Standards.

FEATURES AT A GLANCE

Conforms to the ISO 8528-5 steady-state as well as transient response requirements
Built to accept 100% block load in one step while meeting NFPA 110 loading requirements
Rugged, durable design provides a reliable source of power that handles rough treatment
Proven in-field capability across thousands of applications in an array of work environments

Your one-stop-shop for power equipment solutions.

When you work with React Power Solutions, we have the unique ability to offer custom solutions to the challenges you face on your worksite. Based in Houston, TX, we have everything you need to thrive in challenging work sites.

GENERATOR SET SPECIFICATIONS
Minimum Rating 500 ekW
Maximum Rating 500 ekW
Emissions/Fuel Strategy EPA Stationary Emergency
Voltage 480 to 600 Volts
Frequency 60 Hz
Speed 1800 RPM
Duty Cycle Standby

 

ENGINE SPECIFICATIONS
Engine Model Cat® C15 In-line 6, 4-cycle diesel
Bore 5.4 in
Stroke 6.8 in
Displacement 928 in³
Compression Ratio 16.1:1
Aspiration Turbocharged Air-to-Air Aftercooled
Fuel System MEUI
Governor Type ADEM™A4

 

DIMENSIONS
Length – Maximum 189.6 in
Width – Maximum 64.2 in
Height – Minimum 2034 in
Height – Maximum 101.7 in
Dry Weight – Genset (minimum) 8280.6 lb
Dry Weight – Genset (maximum) 10346.3 lb

 

CAT D500GC Diesel Generator

To get more information on the CAT D500GC Diesel Generator, please send us a quick message and one of our specialists will contact you right away.